← Back
Publicaciones

Parameter identification of a multi-stage, multi-load-demand experimental refrigeration plant

Authors

Rodriguez, David , BEJARANO PELLICER, GUILLERMO, Alfaya, Jose A. , Ortega, Manuel G. , Castano, Fernando

External publication

Si

Means

Control Eng. Practice

Scope

Article

Nature

Científica

JCR Quartile

SJR Quartile

JCR Impact

2.616

SJR Impact

1.069

Publication date

01/03/2017

ISI

000398758900014

Abstract

Parameter estimation of a multi-stage, multi-load-demand refrigeration plant is addressed. It is shown that dominating system dynamics are those of heat exchangers, and their heat-transfer-related parameters affect system statics but barely influence system dynamics. A novel identification procedure focused on the heat exchangers is presented. It is based on non-measurable refrigerant phase-change zones, considering an overall heat transfer coefficient at each zone. Consistent values of all parameters are obtained considering only steadystate experimental data and some orders of magnitude found in the literature. The identified parameters are validated considering the two-stage, two-load-demand plant configuration.

Keywords

Refrigeration system; Vapor compression cycle; Parameter identification; Global validation; Phase-change heat exchanger

Universidad Loyola members