Título Analytical modeling and inertia estimation of VSG-controlled Type 4 WTGs: Power system frequency response investigation
Autores Heidary Yazdi S.S. , Milimonfared J. , Fathi S.H. , ROUZBEHI, KUMARS, Rakhshani E.
Publicación externa No
Medio Int J Electr Power Energy Syst
Alcance Article
Naturaleza Científica
Cuartil JCR 1
Cuartil SJR 1
Impacto JCR 3.58800
Impacto SJR 1.20300
Web https://www.scopus.com/inward/record.uri?eid=2-s2.0-85058161968&doi=10.1016%2fj.ijepes.2018.11.025&partnerID=40&md5=4b71ba10562498e58681ce8de84cafa9
Fecha de publicacion 01/01/2019
ISI 000458221700042
Scopus Id 2-s2.0-85058161968
DOI 10.1016/j.ijepes.2018.11.025
Abstract This paper develops a model to study the inertial dynamics of single Type 4 Wind Turbine Generator (WTG)s that emulate the response of grid-friendly Virtual Synchronous Generator (VSG)s. In this vein, a simplified linearized model is developed for the WTG in the electromechanical time scale considering complete WTG dynamics to obtain/investigate the power System Frequency Response (SFR) characteristics. The objectives are to obtain virtual frequency motion equation, present the mechanism of inertia provision clearly, and feature physical interpretations of inertial frequency response. Accordingly, the available inertia constant and damping coefficient are estimated/expressed analytically in frequency-domain that synthetically embed the impacts of key control parameters as well as the initial operating points. It is realized that the available inertia constant and damping coefficient are adjustable and frequency dependent in contrast to that\'s manifested by a conventional synchronous generator. The developed virtual frequency motion equation is used in turn to establish/investigate the complete SFR model of a generic test power grid which features enormous wind power generation capacity factor. The theoretical analysis shows that the SFR attributes could get adjusted/enhanced by proper tuning of the WTG control parameters. Comprehensive and comparative time domain simulations are also performed in the MATLAB/Simulink platform. It is to verify the accuracy of the proposed models in the evaluation of SFR characteristics and authenticate the theoretical analysis. © 2018
Palabras clave Control system analysis; Damping; Dynamics; Electric power generation; Electric power transmission networks; Equations of motion; Frequency estimation; Frequency response; MATLAB; Synchronous generato