Influence of the ICFF Decoupling Technique on the Stability of the Current Control Loop of a Grid-Tied VSC

Autores

Marin L. , Tarraso A. , Candela I. , Rye R. , RODRÍGUEZ CORTÉS, PEDRO

Publicación externa

No

Medio

IEEE Energy Convers. Congr. Expo., ECCE

Alcance

Capítulo de un Libro

Naturaleza

Científica

Cuartil JCR

Cuartil SJR

Fecha de publicacion

01/01/2019

Scopus Id

2-s2.0-85076750952

Abstract

The control scheme of grid-tied converters is often implemented in the dq-frame due to simplicity of design. However, with this transformation, there exists an inherent cross-coupling term between the d-and q-channels which is often compensated for by using a feed-forward term in the current-control loop. It is shown, by applying the generalized Nyquist criterion (GNC) to the dq-frame ac impedance of the converter, that the inclusion of this decoupling term, in fact, degrades the stability of the controller when increasing the bandwidth of the synchronous reference frame phase-locked loop (SRF-PLL). Harware-in-the-loop (HIL) experiments are also conducted and verify these results. © 2019 IEEE.

Palabras clave

Eigenvalues; Generalized Nyquist criterion; Impedance-based; Inductor current feed-forward; Small-signal; State-space